Skip to content
major vulnerability· requires attention

ICS/OT impact; affects Siemens SIMATIC ET 200 family across manufacturing; could disrupt plant operations.

Infrastructure

CVE-2025-40944

8.7
High
EPSS 0.44%Jan 13, 2026

ICS DoS on SIMATIC ET 200 devices via S7 Disconnect handling flaw.

common questions

Is CVE-2025-40944 being exploited?

Not confirmed. CVE-2025-40944 does not appear in CISA's Known Exploited Vulnerabilities catalog, which records only exploitation that has been observed and reported publicly. That is evidence of absence of a report, not evidence the flaw is unattacked. EPSS currently estimates a 0.44% probability of exploitation in the next 30 days.

How severe is CVE-2025-40944?

CVE-2025-40944 is rated High with a CVSS score of 8.7. Severity describes how bad exploitation would be, not how likely it is: pair it with exploitation evidence before deciding what to patch first.

Is there a patch for CVE-2025-40944?

Not known from our data. No patch reference has been recorded for CVE-2025-40944, which is not the same as no patch existing — a fix may have shipped without a tagged reference, or after this record was written. The vendor advisory is the only authority on whether a fix exists, and mitigations may be available regardless.

What does CVE-2025-40944 affect?

CVE-2025-40944 affects SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), and 6 further products or versions. Confirm the exact affected versions against the vendor advisory before deciding you are exposed.

What should I do about CVE-2025-40944?

Patch when available; restrict S7 access; monitor S7 traffic and PLCs.

Exploitation status reflects CISA's KEV catalog as we last synced it. Check the catalog directly.

executive summary
technical analysis
affected
SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0)SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0)SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3)SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0)SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0)SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0)SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0)SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0)
impact

Remote DoS: valid S7 Disconnect Request on TCP 102 causes devices to hang; reboot required.

action required

Immediate action required

affected versions
Siemens SIMATIC ET 200AL IM 157-1 PN
  • affected< *
Siemens SIMATIC ET 200MP IM 155-5 PN HF
  • affected>= V4.2.0 and < *
Siemens SIMATIC ET 200SP IM 155-6 MF HF
  • affected< *
Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF
  • affected>= V4.2.0 and < V4.2.5
Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF
  • affected< V4.2.2
Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)
  • affected< V1.3
Siemens SIMATIC ET 200SP IM 155-6 PN R1
  • affected< V6.0.1
Siemens SIMATIC PN/MF Coupler
  • affected< *
Siemens SIMATIC PN/PN Coupler
  • affected< V6.0.0
Siemens SIPLUS ET 200MP IM 155-5 PN HF
  • affected>= V4.2.0 and < *
Siemens SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL
  • affected>= V4.2.0 and < *
Siemens SIPLUS ET 200SP IM 155-6 PN HF
  • affected>= V4.2.0 and < V4.2.5
Siemens SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL
  • affected>= V4.2.0 and < V4.2.5
Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAIL
  • affected>= V4.2.0 and < V4.2.5
Siemens SIPLUS NET PN/PN Coupler
  • affected< V6.0.0

As published in the CVE Program record. A version outside these ranges is not a statement that it is unaffected — vendors sometimes understate a range, and distribution-backported builds carry upstream numbers that do not reflect what was patched into them.

how to fix
Remediation steps are tailored for users whose stack is affected. Add this technology to your stack to see the fix checklist.
references
get alerted

Track only the vulnerabilities that affect your infrastructure.

start for free